Medium Voltage Cables Cu or Al/XLPE/CTS/PVC
This cable is used to transmit power on the power transmission and distribution line of A.C.50Hz, rated voltage 36kV or lower. They are appropriate for indoor installations: mostly in power supply stations and outdoors: in cable ducts, underground, and on cable trays for industries, switch-boards and power stations.

Categories:
Medium Voltage Cables
Email:info@zmlcable.com
Introduction
This cable is used to transmit power on the power transmission and distribution line of A.C.50Hz, rated voltage 36kV or lower. They are appropriate for indoor installations: mostly in power supply stations and outdoors: in cable ducts, underground, and on cable trays for industries, switch-boards and power stations.
Instruction of application
Rated Voltage:
● 3.6/6 (7.2) kV
● 6.0/10(12) kV
● 8.7/15(17.5) kV
● 12/20(24) kV
● 18/30(36) kV
● 21/35 kv
●26/35 kv
Conductor
copper/aluminum conductor
Class 2 stranded circular or circular compacted
Semi-Conductive Layer for Conductor
Semi-conductive material
Insulation
XLPE (Cross-Linked Polyethylene)
Semi-Conductive Layer for Insulation
Semi-conductive material
Metallic screen
Copper wires / Copper Tape / Copper Wire & Tape
Outer Sheath
PVC (Polyvinyl Chloride)
The conductor Semi-Conductive Layer, XLPE insulation and the insulation Semi-Conductive Layer are extruded simultaneously in one process using triple extrusion method (Continuous Vulcanization Line). Triple extrusion method not only assures clean interfaces between the insulation and stress control layers, but also assures a construction free of Partial Discharge with high operational reliability.
The Main Technical Parameter Of The Cable
1) Cable conductor DC resistance: See the table 1-1
2) Partial discharge test: See the table 1-2
3) AC voltage test: See the table 1-3
4) Rated Voltage,Core Numbers & Nominal Cross-section Area : See the table1-4
Table 1-1 Max. DC resistance of cable conductor at 200°C
Nominal Area of Conductor |
16 |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
|
Cu(Ω/km) |
Non tinned |
1.15 |
0.727 |
0.524 |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
Tinned |
1.16 |
0.734 |
0.529 |
0.391 |
0.270 |
0.195 |
0.154 |
0.126 |
|
Al (Ω/km) |
1.91 |
1.20 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
|
Nominal Area of Conductor |
185 |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
|
Cu (Ω/km) |
Non tinned |
0.0991 |
0.0754 |
0.0601 |
0.0470 |
0.0366 |
0.0283 |
0.0221 |
0.0176 |
Tinned |
0.100 |
0.0762 |
0.0607 |
0.0475 |
0.0369 |
0.0286 |
0.0224 |
0.0177 |
|
Al ( Ω/km) |
0.164 |
0.125 |
0.100 |
0.0778 |
0.0605 |
0.0469 |
0.0367 |
0.0291 |
Table 1-2 Test Voltage & Max. Discharge capacity of cable
Rated Voltage |
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
Test Voltage |
6.23 |
10.38 |
15.05 |
20.76 |
31.14 |
36.33 |
44.98 |
Discharge capacity |
10 |
10 |
10 |
10 |
10 |
10 |
10 |
Table 1-3 AC voltage test of cable
Rated Voltage |
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
Test Voltage |
12.5 |
21 |
30.5 |
42 |
63 |
73.5 |
91 |
Test Time |
5 |
5 |
5 |
5 |
5 |
5 |
5 |
Table 1-4 Rated Voltage, Core Numbers & Nominal Cross-section Area
U0/Um Area mm2 |
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/20 |
21/35 |
26/35 |
|
Core No. |
1 |
25-630 |
25-630 |
35-630 |
35-630 |
50-630 |
50-630 |
50-630 |
3 |
25-400 |
25-400 |
35-400 |
35-400 |
50-400 |
50-400 |
50-400 |
Key words:
Medium Voltage Cable
Get A Quote
Leave your contact information and get a free product quote
Project Cases
Zhengzhou Zoom Link Cable Co., Ltd. is a high-tech, high-growth, internationalized enterprise with an integrated production plant, integrating R&D, production and sales.
Related Products
Zhengzhou Zoom Link Cable Co., Ltd. is a high-tech, high-growth, internationalized enterprise with an integrated production plant, integrating R&D, production and sales.